| Item | Value |
|---|---|
| Measured gases | LEL flammable gas |
| Measuring range | 0-100% LEL, multi-choice hydrocarbon gas and vapor detection. It can be specially used for the detection of high-concentration gases and volatile solvents |
| Detection principle | infrared |
| Accuracy | |
| Resolution | Hydrocarbons: Baseline<±1% FSD, 50% FSD<±2% FSD Ethylene: Baseline<±2% FSD, 50% FSD<±3% |
| Response time | T50 < 4.5 seconds, T90 < 6.5 seconds (for methane, including weather shield) |
| Ingress protection | IP66/67 |
| Explosion protection | |
| Operating temperature | —40°C to +65°C |
| Power supply | 18-32V (24V normal); 4.5W max |
| Output signal | Multipoint Modbus RS485 (DVC/DX100(m) connection in the middle for communication) |
The Searchpoint Optima Plus is a point infrared hydrocarbon gas detector certified for use in potentially explosive gas atmospheres. The device's infrared detection principle provides the fastest response speed and fail-safe reliable operation, thus ensuring that your plant is safe, protecting your personal safety and maximizing your safe production time and reducing the need for routine maintenance. Requires less operating expense than traditional catalytic combustiongas detectors. Advanced internal fault diagnosis and false alarm immunity design ensure that the Searchpoint Optima Plus provides the highest level of operational integrity.
Searchpoint Optima Plus is widely proven to be a market-leading high-performance, high-sensitivity hydrocarbon flammable gas spot infrared detector.
With more than 40 years of experience in the design, manufacture, installation and maintenance of point infrared gas detectors, Honeywell Analytics has successfully used more than 100,000 point infrared hydrocarbon gas detectors worldwide in a wide range of fields – from light industry to the most demanding offshore oil platforms.
Typical applications for the Searchpoint Optima Plus include environments where catalytic combustion beads may be poisoned or inhibited by substances or environments that require extensive maintenance for commonly used flammable gas detectors, such as: offshore oil and gas platforms, offshore production storage and offloading platforms (FPSOs), tankers, onshore oil and gas platforms, refineries, LNG/LPG tanking plants, Pressure metering stations, gas turbine power stations, solvent printing and coating processes.
Why use infrared technology?
• Reliable operation (fail-safe)
• Fast response time
• Reduced routine maintenance
• No catalytic combustion poisoning
• Long service life
• Can work in an oxygen-free environment
Why Searchpoint OptimaPlus is the right choice...
• With more than 100,000 units of success all over the world
• Higher reliability
• 4-20mA carrier HART® output
• Detects a wide range of hydrocarbon gases, including volatile organic solvents
• No moving components for enhanced reliability
• Optical self-compensating system for enhanced stability
• No long-term drift
• Remote functional gas testing capabilities
• Hazardous area certification worldwide
• More effective prevention of false alarms
• Longer uptime with optical component contamination alarms
• Dynamic heating controller ensures no condensation on the optical surface
• No undetectable faults
• Improved fault diagnosis function
• Complete event log
• Low power consumption
• It has many hazardous area use certifications, including: European (ATEX), UL, CSA, IECEx, CCCF, GB-Ex, etc

Optima Plus Spot Infrared Flammable gas detectors box

Optima Plus point infrared Flammable gas detectors look down
Searchpoint Optima Plusfixed point infrared gas detector technical data 1
Searchpoint Optima Plusfixed point infrared gas detector technical data 2
1. Reliable operation (self-reporting of faults)
2. Fast response time
3. Reduced routine maintenance
4. Immunity to catalytic poisons
5. Long service life
6. Can work in an oxygen-free environment
Searchpoint Optima Plus Specifications :
|
Measurement range |
0-100% LEL, multi-choice hydrocarbon gas and vapor detection. It can be specially used for the detection of high-concentration gases and volatile solvents |
|
Signal output |
4-20mA automatically identifies the source current or leakage current output mode |
|
Inhibition |
1-3mA (2mA default ) |
|
Warnings |
0-6mA (default 3mA*) |
|
Breakdown |
0mA (HART® type regulated to 1mA) |
|
Super Measuring range |
20-21.5mA (21mA default ) |
|
Digital output |
Optional Multipoint Modbus RS485 (via DVC 100(M)), Optional HART Carrier 4-20mA Output (HART Version 7) |
|
Materials |
316 stainless steel |
|
Weight |
1.6kg |
|
Precision Optima Plus (hydrocarbon-based gases) Optima Plus (Ethylene) |
Baseline < ±1% FSD, 50% FSD <± 2% FSD Baseline < ±2% FSD, 50% FSD <± 3% FSD |
|
Repeatability |
< ±2% FSD, 50% FSD |
|
Linearity |
< 5% FSD |
|
Response time |
Compliant with EN60079-29-1 (ATEX Performance Standard) T50 < 3 seconds, T90 < 4 seconds |
|
Certified scope of work |
-40°C to +65°C temperature range |
|
Time and temperature range effects Generated drift |
-40°C to +65°C Baseline< ±2% FSD 50% FSD < ±4% FSD |
|
Vibration deviation |
0.1% (reading) per millibar |
|
Power Supply |
18-32Vdc (24Vdc normal), < 4.5W max |
|
Ingress protection |
IP 66 / 67 |
|
Diagnosis (Recalibration) |
Operation is achieved via certified hand operator or optional HART® communication |
|
Hazardous Area Certification |
ATEX: BAS99ATEX2259X II 2 GD Ex d IIC Gb Ex tb IIIC Db T96℃ (Tamb -40°C to +65°C) T86℃ (Tamb -40°C to +55°C) IP 66/67 UL / CSA: Class 1, Zone 1, Group B, C, and D (-40°C to +65°C) IECEx: Ex d IIC tb IIIC T86℃ (Tamb -40°C to +55°C) or T96°C (Tamb -40°C to +65°C) IP66/67 |
|
Performance Licensing |
EN 60079-29-1 (BVS 03 ATEX G 016 X), CSA C22.2 152. |
|
Functional safety |
IEC61508 Safety Integrity Level 2 |
|
EMC compatibility |
EN 50270:2006 EN 50271:2010 |

Optima Plus dots infrared Flammable gas detectors on the side

Optima Plus points infrared Flammable gas detectors on the side
0-100% LEL, multi-choice hydrocarbon gas and vapor detection. It can be specially used for the detection of high-concentration gases and volatile solvents
Commercial: parking garage, computer room, cooler, office business, shopping center, swimming pool, school, university and laboratory
Industrial applications: petrochemical, metallurgy, steel boiler rooms, commercial plants, refrigeration equipment, offshore drilling platforms and semiconductor production workshops