| Item | Value |
|---|---|
| Measured gases | |
| Measuring range | |
| Detection principle | |
| Accuracy | |
| Resolution | |
| Response time | |
| Ingress protection | |
| Explosion protection | |
| Operating temperature | |
| Power supply | |
| Output signal |
HMS-FD-3IR uses high-quality multi-infrared sensing technology (MIR), using different wavelength infrared sensors with narrowband filtering, one of which works at the center wavelength reflecting the flame information, and the other two sensors monitor other infrared radiation in the environment, combined with the flickering characteristics of the flame, through high-performance microprocessor and good mathematical algorithm model for computational analysis, so that only the radiation spectrum that meets the flame characteristics will be confirmed as a fire alarm, False fire alarm signals formed by other interfering factors will be excluded.
• Uses high-quality multi-infrared sensing technology
• High-performance microprocessors and high-quality mathematical algorithm models
• High anti-interference ability, accurately identifying the radiation spectrum that matches the flame characteristics
• It has a good inhibition effect on interference such as sunlight, lightning, electric welding, artificial light sources, environment (people, etc.), heat radiation, electromagnetic interference, and mechanical vibration
• The detector alarm sensitivity is divided into four levels to meet the needs of different places.
|
|
|
|
|
Field of view |
90°, 100%Fully conical field of view; Central axis±45° |
|
|
Sensitivity |
Class I, Class II, Class III, Level IV (Default Level II, Level IV) |
|
|
Response time |
60Rice place0.1square meters of n-heptane flame3~5seconds |
|
|
Corresponding spectral range |
3.8um ~ 5.0um |
|
|
Explosion-proof sign |
Exd ⅡC T6 Gb/Ex tD A21 IP66 T80℃ |
|
|
Ingress protection |
IP66 |
|
|
Operating voltage |
DC18V~30V (Nominal valueDC24V) |
|
|
Operating current |
≤35mA (24VDC) |
|
|
Signal output |
The relay has no passive point |
|
|
Analog output 0~20mA |
0mA Power failure, open circuit or short circuit; or DC voltage below18VDC; 2mA detector Detector Detects Mirror Contamination or Automatic Detection of Light Source Signal Weakening 4mA Normal 20mA Call the police |
or internal circuit failure |
|
Digital communication Indicator light |
Hart*, MODBUS, Fire Bus Green LED indicator: power; Red LED indicator: alarm; Yellow LED indicator: fault; |
|
|
Installation method: Heavy Quantity |
Wall mounted or hoisted 2.0±0.2 kg (Cast Aluminum) |
|
|
Outside shell |
Copper-free cast aluminum, surface epoxy resin baking paint treatment. Stainless steel optional*. |
|
|
Cable entry device interface |
Two are standardNPT3/4”interface |
|
|
Ambient temperature |
-40°C~+70°C |
|
|
Relative humidity |
≤95%RH(No condensation) |
|
|
Certification |
CCCF, Ex |
|
|
*Please check with the Honeywell office |
Recognize |
|
• Hangars
• Aircraft repair yards
• Chemical industry
• Highway tunnels
• Ammunition and explosives warehouses
• Paint factory
• Petrochemical enterprises
• Pharmaceutical companies
• Power stations
• Printing enterprises
• Flammable material warehouses